Operation Section
23
5.3 Power Supply Requirements
(1) Power supply
AC 460 V ± 10 %, 3 phase and 60 Hz. Do not connect the unit to any other power supply.
• The power supply should be a dedicated single outlet circuit with a UL approved short-circuit
and ground fault protective breaker with a recommended fuse size of 20 A (20 A maximum).
Securely tighten each terminal.
CAUTION
Use a specified 20 A fuse. Do not use wiring, copper wire or soldering instead of the fuse. The
use of non-specified fuses can cause machine failure or fire.
I003021
Circuit Breaker With
Ground-Fault Protective
Grounding
Terminal
Green
Colored Wire
Fuse 20 A (20 A MAX.)
RSTG
RSTG
Terminal Block of Classic 60
Power Source
AC 460 V, 3 Phase, 60 Hz